Components:

A. (3) - #1 AWG Class B stranded, 8000 series, aluminum conductors w/50 mils (1.27 mm) heat and moisture resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 7 mils (0.18 mm) nylon applied directly to the surface of the insulation.

 

B. (9) - #18 AWG Class K stranded, soft drawn, bare copper conductors w/15 mils (0.38 mm) heat and moisture resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 4 mils (0.10 mm) nylon applied directly to the surface of the insulation.

 

C. (1) - #6 AWG Class B stranded, 8000 series, aluminum conductor w/30 mils (0.76 mm) heat and moisture resistant, polyvinyl chloride (PVC) insulation and jacketed w/ 5 mils (0.13 mm) nylon applied directly to the surface of the insulation.

 

D: Mylar binder tape.

 

E. 1.80 mils (2.03mm) of heat and moisture resistant, polyvinyl chloride (PVC) jacket. A rip cord shall be placed underneath the jacket.

 

Print Legend

(UL) E60544 POWER AND CONTROL TRAY CABLE TYPE TC-ER-JP 1 AWG AL (42,4 mm2) 3/C + 6 AWG AL (13,3 mm2) 1/C GROUND THWN CONDS & 18 AWG (0,82 mm2) 9/C TFFN CONDS 600V 75C DRY/75C WET OIL RES I SUNLIGHT RESISTANCE DIRECT BURIAL JOIST PULL P/N 1624-1000 "sequential footage print"

 

Electrical / Optical Characteristics

Voltage: 600V

 

Specifications

Conductors: ASTM B 3, ASTM B 174, ASTM B 801

 

Insulation: ICEA S-95-658 (NEMA WC 70), ICEA S-73-532 (NEMA WC 57), UL 83 for Type THWN wires

 

Jacket: ICEA S-95-658 (NEMA WC 70), ICEA S-73-532 (NEMA WC 57), UL 1277

 

Ratings:

UL Standard: 1277

UL: 1685

UL: TC-ER-JP 600VNEC/NFPA: 2023 / 336.10(9)

UL: THWN 600V

 

The insulation is acceptable for use in locations at 75 °C dry and 75 °C wet. The cable is suitable for use in cable trays, aerial or direct burial installations. The cable is JP rated for installation in accordance with Part II of Article 334.

 

Commonly used with 17-24kW 26kW NG +2

#1 x 3 TCERJP Aluminum 9W Generator Wire #6 x 1, #18 x 9